Modular Redundant Power Supply Systems
using Linear Regulated Power Supplies
AC-DC single output
- Shipped Within 9 Days
- Five Year Warranty
Specifications
Input Voltage: 105-125 VAC, 50-400 Hz, single phase.
A separate set of AC input terminals is provided for each power supply,
so that if two sources of AC input power are available, one may be used
for each supply and so reduce the possibility of output dropout due to loss
of input power.
Output Voltage:
Normal mode: Nominal
voltage shown in table.
Backup mode: 0.2 volt
less than nominal voltage shown in table.
Load Regulation: ±0.05% (Dynamic regulation - does not include 0.2 volt shift which occurs during switchover to lower-set backup supply.)
Line Regulation: ±0.05%
Ripple: 1 mV rms.
Remote Voltage Sensing: Provision for sensing the output voltage across the load, so that drops in the load line are compensated, is a standard feature.
Load Protection: Overvoltage protection.
Overload/Short Circuit Protection: Foldback current limiting with automatic recovery.
Polarity: Output is floating; either positive or negative output terminal may be grounded or floated up to 300 volts above ground.
Output Monitoring: Output Present LED for each power supply is located on the Integration Module.
Alarm Relay Contact Ratings: 120 VAC, 8A / 60 Vdc, 1A. (To comply with SELV requirements, limit switched voltage to 60 Vdc / 42 VAC.)
Terminal Strip Cover: Clips on.
Interconnection: The Integration Module has two 24 inch long cables.
Temperature Coefficient: 0.02%/°C (Typical).
Ambient Operating Temperature: 20 to +71°C.
Storage Temperature: 55 to +85°C.
Mounting: Threaded mounting holes permit mounting to a chassis,
cabinet wall or bracket, or they may be used on a test bench or tabletop.
To mount from the power supply side of the mounting surface or for DIN rail
mounting, see Accessory Mounting Kits.